Panasonic FP7 User Manual page 79

High-speed counter unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

 Setting items and corresponding unit memory numbers
Unit
memory
No.
(Hex)
UM 00100
UM 001D0
External output 0 signal
setting
UM 002A0
UM 00370
UM 00101
UM 001D1
Output hold setting of
external output 0 signal
UM 002A1
UM 00371
UM 00102
External output 0 signal
ON timing delay
UM 001D2
(Available when band
UM 002A2
comparison function is
used)
UM 00372
UM 00103
External output 0 signal
ON hold time
UM 001D3
(Available when band
UM 002A3
comparison function is
used)
UM 00373
UM 00104
UM 001D4
External output 1 signal
setting
UM 002A4
UM 00374
UM 00105
UM 001D5
Output hold setting of
external output 1 signal
UM 002A5
UM 00375
UM 00106
External output 1 signal
ON timing delay
UM 001D6
(Available when band
UM 002A6
comparison function is
used)
UM 00376
UM 00107
External output 1 signal
ON hold time
UM 001D7
(Available when band
UM 002A7
comparison function is
used)
UM 00377
(Note) The unit memory numbers in the above table are for CH0, CH1, CH2 and CH3 from the top.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Default
H0
H0
0
0
H0
H0
0
0
Setting range and description
Set whether or not to output the comparison
match 0 flag to the external output 0 signal.
H0: Not output
H1: Output
Set whether or not to hold the output signal in the
program mode when an error occurs.
H0: Not hold
H1: Hold
Set the ON timing delay of external output 0
signal.
Setting range: 0 to 1,000(The values out of the
setting range are invalid.)
Set the ON hold time of external output 0 signal.
Setting range: 0 to 1,000 (The values out of the
setting range are invalid.)
Set whether or not to output the comparison
match 1 flag to the external output 1 signal.
H0: Not output
H1: Output
Set whether or not to hold the output signal in the
program mode when an error occurs.
H0: Not hold
H1: Hold
Set the ON timing delay of external output 1
signal.
Setting range: 0 to 1,000 (The values out of the
setting range are invalid.)
Set the ON hold time of external output 1 signal.
Setting range: 0 to 1,000 (The values out of the
setting range are invalid.)
Unit
ms
ms
ms
ms

Advertisement