 Count function
Unit
memory
No.(Hex)
UM 00056
UM 00126
Specify count
direction
UM 001F6
UM 002C6
UM 00057
UM 00127
Select count input
UM 001F7
UM 002C7
UM 00058
UM 00128
Count method
UM 001F8
UM 002C8
UM 00059
UM 00129
Input Z signal
function setting
UM 001F9
UM 002C9
UM 0005A
UM 0012A
Control 0 signal
function setting
UM 001FA
UM 002CA
UM 0005B
UM 0012B
Control 1 signal
function setting
UM 001FB
UM 002CB
(Note) The unit memory numbers in the above table are for CH0, CH1, CH2 and CH3 from the top.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Default
H0
H0
H0
H0
H0
H0
Setting range and description
Set the direction of count.
H0: Count in normal direction
H1: Count in reverse direction
Select a signal for counting from the count signal,
internal clock or internal control signal.
H0: Count signal
H1: Internal clock 0.25 us (4 MHz)
H2: Internal clock 1.00 us (1 MHz)
H3: Internal clock 10 us (100 kHz)
H4: Internal clock 100 us (10 kHz)
H7: Internal control signal
Set the count method.
H0: 2-phase input 1 multiple
H1: 2-phase input 2 multiple
H2: 2-phase input 4 multiple
H3: Individual input 1 multiple
H4: Individual input 2 multiple
H5: Direction detection input 1 multiple
H6: Direction detection input 2 multiple
Set counter operations by the input Z signal.
H0: Not used
H1: Reset operation at rising edge
H2: Reset operation at trailing edge
H3: Positive logic reset operation
H4: Negative logic reset operation
H5:Preset operation at rising edge
H6:Preset operation at trailing edge
H7: Positive logic preset operation
H8: Negative logic preset operation
Set counter operations by the control 0 signal.
H0: Not used
H1: Positive logic enable operation
H2: Negative logic enable operation
H3: Positive logic enable operation, reset operation
at rising edge
H4: Negative logic enable operation and reset
operation at trailing edge
H5: Positive logic enable operation and preset
operation at rising edge
H6: Negative logic enable operation and preset
operation at trailing edge
Set counter operations by the control 1 signal.
H0: Not used
H1: Positive logic enable operation
H2: Negative logic enable operation