5.1 Selection of Counters and Basic Settings

5.1.1 Basic Settings of Counters

The basic settings are set in the configuration menu of FPWIN GR7 or unit memories (UM).
 Count function configuration
Item
Counter type
Enable/Disable
overflow/underflow
Counter upper limit
Counter lower limit
Specify count direction
Select count input
Count method
 Example of settings by FPWIN GR7

5.1.2 Selection of Count Input

• Select the count input to import input signals from an external device.
• For measuring the frequencies of external input signals or time based on the internal clock of
the unit, select "Internal clock".
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Linear counter/Ring counter
Disable/Enable
-2,147,483,647 to 2,147,483,647
-2,147,483,648 to 2,147,483,646
Normal direction/Reverse direction
Count signal / Internal clock 0.25 us (4 MHz) /
Internal clock 1.00 us (1 MHz) / Internal clock 10us (100
kHz) / Internal clock 100 us (10 kHz)
2-phase input 1 multiple, 2-phase input 2 multiple, 2-phase
input 4 multiple, Individual input 1 multiple, Individual input 2
multiple, Direction detection input 1 multiple, Direction
detection input 2 multiple
Default
Linear counter
Disable
2,147,483,647
-2,147,483,648
Normal direction
Count signal
2-phase input 1
multiple