6.1.2 Configuration

For using the measurement function, set the following items using the configuration menu of
tool software FPWIN GR7 or user programs.
 Setting area
Unit
memory
No.
(Hex)
UM 00070
UM 00140
Select measurement
UM 00210
function
UM 002E0
UM 00071
UM 00072
UM 00141
UM 00142
Pulse number per
rotation
UM 00211
UM 00212
UM 002E1
UM 002E2
UM 00073
Set averange
UM 00143
number of frequency
UM 00213
measurement
UM 002E3
processes
UM 00074
Set average number
UM 00144
of rotation speed
UM 00214
measurement
UM 002E4
processes
(Note) The unit memory numbers in the above table are for CH0, CH1, CH2 and CH3 from the top.
 Example of settings by FPWIN GR7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Default
H0
U1
H0
H0
Setting range and description
H0: Not use measurement function
H1: Frequency measurement
H2: Frequency measurement and rotation speed
measurement A
H3: Frequency measurement and rotation speed
measurement B
Set the pulse number for one rotation of the encoder.
Setting range: 1 to 1,048,575 (The values out of the
setting range are invalid.)
Set the number of averaging of frequency measurement
values.
H0: No averaging, H1: 2 times, H2: 4 times, H3: 8 times,
H4: 16 times, H5: 32 times, H6: 64 times, H7: 128 times
Set the number of averaging of rotation speed
measurement values.
H0: No averaging, H1: 2 times, H2: 4 times, H3: 8 times,
H4: 16 times, H5: 32 times, H6: 64 times, H7: 128 times
Unit
Pulse
Times
Times