5.19 MULTI-FUNCTION OUTPUT TERMINALS (Term, MA, MB & MC; P1, P2 & PC)
Set
Value
Condition
0
Fault
1
During operation
2
Speed at set frequency
3
Zero Speed
4
Frequency detection - low
5
Frequency detection - high
6
Overtorque detection
(N.O. contact)
7
Overtorque detection
(N.C. contact)
8
Under torque detection (NO)
9
Under torque detection (NC)
10
Alarm (minor fault)
11
During coast to stop
12
Local/Remote
13
Operation ready
14
Auto-restart
15
During Undervoltage
16
During Reverse run
17
During Speed Search
18
Serial communication
20
Frequency reference is missing
21
Inverter overheating pre-alarm OH3 Closed if drive overheat pre-alarm is input at a Multi-function
Table 5-3. Multi-function Output Terminals
Description
Closed = Drive fault has occurred (except CPF00, CPF01)
Closed = Drive is operating
Closed = Frequency Reference = output frequency
See paragraph 5.19A
Closed = Drive is at zero Hz.
Closed = Output frequency ≤ n095.
See paragraph 5.19B
Closed = Output frequency ≥ n095.
See paragraph 5.19C
Closed = Overtorque detected
See paragraph 5.20
Open = Overtorque detected
See paragraph 5.20
Closed if under torque is detected
Open if under torque is detected
Closed = Alarm condition is present
Closed = Drive output base block is active; motor is coasting
Open = Frequency and Run Command by ext. input;
Closed = Frequency and Run Command by Digital Operator
Closed = Drive is ready for operation (not faulted)
Closed = During auto-restart operation
Closed = Drive has an undervoltage fault or warning.
Closed = Drive operation in reverse
Closed = Drive performing a speed search
Closed = Command from serial communication
Closed if frequency reference is missing
Input. Digital operator display is "OH3" (blinking)
5-29