YASKAWA V7 Technical Manual page 123

Hide thumbs Also See for V7:
Table of Contents

Advertisement

PARA-
METER
NAME
Multi-function Input
n053
Selection 4 (Terminal S4)
Multi-function Input
n054
Selection 5 (Terminal S5)
Multi-function Input
n055
Selection 6 (Terminal S6)
n056
Multi-function Input
Selection 7 (Terminal S7)
Multi-Function Output
n057
Selection 1
(Terminals MA, MB & MC)
Multi-Function Output
n058
Selection 2
(Terminals P1 & PC)
Multi-Function Output
n059
Selection 3
(Terminals P2 & PC)
``
Analog Frequency Reference
n060
Gain (term. FR to FC) (Note 4)
Analog Frequency Reference
n061
Bias (term. FR to FC) (Note 4)
Analog frequency reference
n062
filter time constant
(term. FR to FC) (Note 4)
Frequency Reference Loss
n064
Detection
Monitor Output0:
n065
Selection
Multi-function Analog Output
n066
(Terminals AM & AC)
n067
Analog Monitor Gain (Note 4)
Analog Frequency Reference
n068
Gain (CN2, Voltage Ref Input)
Analog Frequency Reference
n069
Bias (CN2, Voltage Ref Input)
Table A1-1. Drive Parameters - Continued
SETTING RANGE
(AND UNITS)
9:
Multi-step speed ref. cmd. D
10: JOG Selection
11: Accel/Decel time change cmd.
12: External Base Block (N.O.)
13: External Base Block (N.C.)
14: Speed search from max. freq.
15: Speed search from set freq.
16: Accel/Decel hold command
17: Remote/Local selection
18: Serial Communication / control ckt.
selection
19: Fast Stop - Fault (N.O.)
20: Fast Stop - Alarm (N.O.)
21: Fast Stop - Fault (N.C.)
22: Fast Stop - Alarm (N.C.)
23: PID control off
24: I value reset (PID)
25: I value hold (PID)
26: Over Heat Pre-alarm OH3
27: Accel/Decel Time Select 2
34: Up
0:
Fault
1:
During running
2:
Speed Agree
3:
Zero Speed
4:
Frequency detection 1
5:
Frequency detection 2
6:
Overtorque detection (N.O.)
7:
Overtorque detection (N.C.)
8:
Undertorque Detection (N.O.)
9:
Undertorque Detection (N.C.)
10: Minor Fault
11: During Base Block
12: Local / Remote
13: Ready
14: During auto restart
15: During undervoltage
16: During reverse run
17: During speed search 1
18: Serial Comm. Controlled
19: PID feedback loss
20: Frequency Reference Loss Detect (N.O.)
21: Overheat Pre-alarm OH3 (N.O.)
0 to 255
-100 to 100
0.00 to 2.00
0:
No Detection
1:
Continue to run at 80% of max. frequency
Analog monitor output
1:
Pulse monitor output
0:
Output frequency (10V = 100% Fmax)
1:
Output Current (10V = 100% drive
rated current)
2:
DC Bus Voltage
(10V = 400 VDC [800 VDC])
3:
Motor Torque
(10V = Motor rated torque)
4:
Output Power
(10V = Drive Capacity kW)
5:
Output Voltage 10V = n012 (voltage max)
6:
Frequency Reference
0.00 to 2.00
-255 to 255
-100 to 100
A1-3
SETTING
FACTORY
USER
INCREMENT
SETTING
SETTING
1
5
(5)
1
6
(6)
1
7
(7)
1
10
(10)
1
0
1
1
2
1 (%)
100
1 (%)
0
0.01 (sec)
0.10
1
0
1
0
1
0
0.01
1.00
1%
100
1%
0
PARA.
REF.
5.18
5.19
5.8
5.33
5.17
5.17
5.32