YASKAWA V7 Technical Manual page 30

Hide thumbs Also See for V7:
Table of Contents

Advertisement

1.4 ELECTRICAL INSTALLATION
E. Conformance to European EMC Directive
In order to conform to EMC standards, the following methods are required for line filter application,
cable shielding and drive installation.
The line filter and Drive must be mounted on the same metal plate. The filter should be mounted as
close to the drive as practical. The cable must be kept as short as possible and the metal plate
should be securely grounded. The ground of the line filter and the drive must be bonded to the
metal plate with as much bare-metal contact as possible.
For main circuit input cables, a screened cable is recommended within the panel and is also
suggested for external connections. The screen of the cable should be connected to a solid ground.
For the motor cables, a screened cable (max. 20 m) must be used and the screen of the motor cable
should be connected to ground at both ends by a short connection, again using as much bare-metal
contact as practical.
For a more detailed explanation, refer to the manufacturer document EZZ006543, "Installation
Guidelines For EMC Directive using AC Drive Products."
Table 1-4 and Figure 1-4 show the line filter list for EMC standards and the installation/wiring of the
Drive and line filter.
Model
CIMR-
Part Number
V7*
MV
FIL00
20P1
A001
20P2
A002
20P4
A003
20P7
A005
21P5
A008
22P2
A011
23P7
A017
25P5
A025
27P5
A033
40P2
B001
40P4
B002
40P7
B003
41P5
B005
42P2
43P7
B009
45P5
B015
47P5
(1)
D is the distance the filter will extend outward from the surface of the metal plate.
Table 1-4. Line Filters for EMC Standards
Rated
Weight
Current (A)
lbs. (kg)
1083
10
1.8 (0.8)
1084
16
2.2 (1.0) 6.7 x 4.4 x 2.0 (169 x 111 x 50)
1085
26
2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50) 6.3 x 4.7 (161 x 120)
1100
50
5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150)
1086
5
2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)
1087
10
2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)
1088
15
2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50) 6.3 x 4.7 (161 x 120)
1101
30
5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150)
D
Continued
Line Filter
Dimensions in in. (mm)
H x W x D
7.6 x 3.2 x 2.0 (194 x 82 x 50)
4-d
H1
W1
W
1-12
Mounting Dim. in in. (mm)
(1)
H1 x W1
7.1 x 2.4 (181 x 62)
6.1 x 3.6 (156 x 91)
6.1 x 3.6 (156 x 91)
6.1 x 3.6 (156 x 91)
H
Screw
Size
M5
M5
M5
M6
M5
M5
M5
M6