Motor overload protection
Instantaneous overcurrent
Overload
Overvoltage
Undervoltage
Momentary Power Loss
Heatsink overheat
Stall prevention level
Ground fault
Power charge indication
Cooling Fan Fault
Run/stop input
Multi-function input
Multi-function output
Analog monitor
Standard functions
Status indicator LEDs
Digital Operator
Terminals
Wiring distance between
drive and motor
Enclosure
Cooling method
Ambient temperature
Humidity
Storage temperature (4)
Location
Elevation
Vibration
NOTES:
(1)
Based on an N.E.C. standard 4-pole motor for max. applicable motor output.
(2)
Shows deceleration torque for an uncoupled motor decelerating from 60 Hz in 0.1 seconds.
(3)
Contact Yaskawa for wiring distances greater than 328 ft. (100 m).
(4)
Temperature during shipping (for short periods of time).
(5)
On NEMA type 4X/12 model only, maximum continuous rating of 30.8 A is 40 degrees C maximum ambient. For 33.0 A maximum
continuous rating, maximum ambient is 32 degrees C.
(6)
Applies to NEMA type 4X/12 model only.
(7)
On Model 47P5 NEMA type 4X/12 (21A), overload is 120% for 1 minute.
Table A2-1. Standard Specifications (Continued)
SECTION B. All Drives (Continued)
during undervoltage detection, minor error, during baseblock, operation mode,
inverter run ready, during fault retry, during UV, during speed search,
0 to +10VDC output, programmable for output frequency or output current
Open Loop Vector Control, full-range automatic torque boost, auto restart,
upper/lower frequency limit, DC injection braking current/time at start/stop,
analog meter calibrating gain, S-curve accel/decel, slip compensation,
Electronic thermal overload relay
Motor coasts to stop at approx. 250%
of drive current
Motor coasts to stop after 1 min. at 150% of
drive rated current (7)
Motor coasts to stop if DC bus voltage exceeds
410VDC (230V), 820VDC (460V)
Motor coasts to stop when DC bus voltage is
210VDC or less (230V), 400VDC or less (460V)
The following operations are selectable:
• Not provided (stops if power loss is 15 ms or longer)
• Automatic restart at recovery from 0.5 sec. power loss
• Automatic restart
Protected by electronic circuit
Independently programmable during accel and
constant-speed running. Selectable during decel.
Protected by electronic circuit (overcurrent level)
ON until the DC bus voltage becomes 50V or less.
RUN lamp says ON or digital operator LED stays ON.
(Charge LED is Provided for 400V)
Protected by electronic circuit
2-Wire or 3-Wire
Seven of the following input signals are selectable:
Forward/reverse run (3-Wire sequence), fault reset,
external fault (NO/NC contact input), multi-step speed operation,
Jog command, accel/decel time select,
external baseblock (NO/NC contact input, speed search command,
accel/decel hold command, LOCAL/REMOTE selection,
communication/control circuit terminal selection,
emergency stop fault emergency stop alarm
Following output signals are selectable
(1 NO/NC contact output, 2 photo-coupler outputs):
Fault, running, zero speed, at frequency, frequency detection
(output frequency ≤ or ≥ set value), during overtorque detection,
data output through communication
frequency reference gain/bias, prohibited frequencies,
MODBUS communications (RS485/422, Max. 19.2K bps),
frequency reference from digital operator pot
RUN and ALARM LEDs provided as standard
Monitors frequency reference, output frequency,
output current, FWD/REF selection
Screw terminals for both main circuit and control circuit
328 ft (100 m) or less (3)
Open Type/NEMA type 1/NEMA type 4X/12
Self-cooling/cooling fan
14 to 104°F (-10 to 40°C)
95% RH or less (non-condensing)
-4 to 140°F (-20 to 60°C)
Indoor (free from corrosive gases or dust)
3,280 feet (1,000 m) or less
Up to 1G, at less than 20 Hz;
up to 0.2G, at 20 to 50 Hz
A2-2