1.4 ELECTRICAL INSTALLATION
3-PHASE
POWER SUPPLY
(Use L1 (R) and
L2 (S) for
L1
single-phase
input)
L2
(Note that drive must
be derated by 50%
L3
on 3-Phase Models)
FORWARD
RUN/STOP
REVERSE
RUN/STOP
*
EXTERNAL
1OL
FAULT
See
Note 3)
FAULT
RESET
MULTI-STEP
SPEED REF 1
MULTI-STEP
SPEED REF 2
JOG REFERENCE
FREQUENCY
MANUAL
REF.
SPEED
(See Note 5)
0-10VDC
4-20mA
MODBUS
COMMUNICATIONS
RS485/422
19.2 KBPS MAX.
Figure 1-5. Standard Connections (2-Wire Control)
H. Inspection. After wiring is complete, verify that all wiring is correctly installed,
excess screws and wire clippings are removed from inside of unit, screws are
securely tightened, and exposed wire does not contact other wiring or terminals.
If a FWD or REV run command is given from the control
circuit terminal when the operation method selection
function ( n003 ) is set to " 1 " and the "LO/RE" selection
is set to "RE", the motor will start automatically as soon
as power is applied to the main circuit.
FOR DC REACTOR
(See Note 7)
1-3FU*
+1
*
MCCB
(See Note 9)
L1 ( R )
L2 ( S )
L3 ( T )
S1
(See Note 8)
(See Note 5)
S2
MULTI-FUNCTION
S5
S6
S7
LOGIC
COMMON
SC
TERMINAL
(See Note 1)
SHIELD
CONNECTION
PULSE TRAIN INPUT
RP
(MAX 30KHz)
*
1R
2KΩ
FREQUENCY
FS
SETTING POWER SUPPLY
*
1RH
REFERENCE
FR
2KΩ
FC
OV
or
+
R+
R-
MODBUS
(TERMINAL
S+
RESISTANCE:
120Ω, 0.5W)
S-
(Parameter n001 set to "10")
CAUTION
1-15
Continued
FOR DYNAMIC BRAKING
(See Note 6)
+2
B1
T1 ( U )
T2 ( V )
T3 ( W )
V7
OR
V74X
S3
ANALOG MONITOR
S4
CONTACT INPUT
(+12V, 20mA) (See Note 2)
(0 to 10V, 20KΩ /
4 to 20mA, 250Ω)
FREQUENCY
SETTING
POT
MIN
SW1
SW2
PNP
OFF
NPN
V
B2
*
1OL (See Note 3)
*
AC
MOTOR
(See Note 4)
ANALOG OUTPUT
MONITOR 0 to +10VDC
AM
*
FM
OUTPUT
AC
FREQUENCY
MA
MULTI-FUNCTION
OUTPUT CONTACT
MB
250VAC, 1A OR LESS
FAULT
MC
30VDC, 1A OR LESS
MULTI-FUNCTION
P1
PHOTOCOUPLER
RUNNING
OUTPUT
PC
48V, 50mA OR LESS
SPEED
COINCIDENCE
P2
MAX
1 ON
2
I
FIG. 1-9