YASKAWA V7 Technical Manual page 11

Hide thumbs Also See for V7:
Table of Contents

Advertisement

Example 3: Remote Sequence (3-Wire) & Local Reference (Digital
Operator)
This configuration is best when a person rather than an external controller (PLC, relay, etc.) controls the drive.
OPERATION:
The frequency reference comes from the digital operator pot.
Close pushbutton (PB1) momentarily while pushbutton (PB2) is closed, and the drive will run at the
frequency setting in U1-01. Pushbutton (PB1) does NOT need to be maintained.
Open pushbutton (PB2) at any time and the drive will stop.
If switch (SW1) is open, the drive will run in the forward direction. If switch (SW1) is closed, the drive will
run in the reverse direction. Switch (SW1) can be operated with the drive running at any speed.
If the drive is put in the "Local" mode using the LO/RE quick start LED, the drive will behave the same as
illustrated in Example 1.
Table 4: Programming Required For Remote 3-wire Sequence & Local Reference
Parameter
n001
n001
n004
n036
Set Motor FLA
Control Wiring Schematic
FS
0.00
FREF
FOUT
IOUT
MNTR
FR
F/R
LO/RE
PRGM
DSPL
RUN
FC
STOP
DATA
ENTER
RESET
Display
Description
The drive will perform a 3-wire reset.
11
Setting this value will reset all parameters to their original factory
settings (all previous adjustments will be lost). When the drive
completes the reset, this parameter returns to a value of 1.
After doing the reset above, the password parameter returned to a
4
1. Change it to a 4 to get access to all parameters in the drive.
This parameter sets the reference (motor speed) to come from the
0
digital operator potentiometer (local).
Enter the motor's full load amps (as shown on the motor
nameplate).
(PB1)
S1
START
(PB2)
S2
STOP
(SW1)
S3
FOR/REV
S4
MIN
MAX
S5
Shield (Drain Wire)
S6
S7
SC
CAUTION
- ix -
Start
Stop
Forward
Reverse
To Terminal