5.17 MULTI-FUNCTION ANALOG MONITOR OUTPUT (Term. AM & AC)
n067 : Analog Monitor Gain
This constant is used to calibrate the meter connected to terminals AM & AC.
MAX. OUTPUT
FREQUENCY
OR CURRENT.
n150 : Pulse Monitor Output
Frequency Output/Reference
SETTING
DESCRIPTION
0
1140Hz/ Max. frequency (n011)
1
1F: Output frequency x 1
6
6F: Output frequency x 6
12
12F: Output frequency x 12
24
24F: Output frequency x 24
36
36F: Output frequency x 36
40
1140Hz/Max. frequency (n011)
41
1F: Frequency reference x 1
42
6F: Frequency reference x 6
43
12F: Frequency reference x 12
44
24F: Frequency reference x 24
45
36F: Frequency reference x 36
At the factory setting of "0" a pulse train frequency of 1440 Hz will be output when output frequency
is 100% .
AM
AC
When connecting peripheral devices the following load limitations must be considered.
When using output as a sourcing output:
Max output voltage (V)
Load Impedence (K ohms)
+5V
1.5K ohms to 3.499K ohms
+8V
3.5K ohms to 9.99K ohms
+10V
10K ohms or more
When used as a sinking input:
External power supply (v)
Sinking current (mA)
100%
0
3 V
ANALOG OUTPUT
100 %
Pulse
Pulse monitor output
+12VDC +/-5%
16mA or less
5-21
Continued
Factory Setting: 1.00
Range: 0.01 to 2.00
n067 = 0.30
Factory Setting
(n067 = 1.00)
10 V
Factory Setting: 0
Range: 0, 1, 6, 12, 24, 36, 40 - 45
1440 Hz