Wiring And Connecting Profibus Connectors - Siemens SIDOOR ATD401W System Manual

Atd4xxw series, door control systems for industrial applications
Hide thumbs Also See for SIDOOR ATD401W:
Table of Contents

Advertisement

4.5.3.2

Wiring and connecting PROFIBUS connectors

Requirement
NOTICE
PROFIBUS connector
Use only the recommended PROFIBUS connectors from Siemens. For more, see also
section Accessories (Page 21).
NOTICE
Material damage resulting from the connection of a PROFIBUS connector to service
connection X8
Connecting a PROFIBUS connector to service connection X8 can damage the SIDOOR
controller and the connected device.
For this reason, only connect a bus connector to connection X705.
Note
• Always use shielded cables.
• For stationary operation, it is advisable to remove the insulation of the shielded cable and
to establish contact on the shield/PE conductor bar.
• If there is a potential difference between the grounding points, an impermissibly high
compensating current can flow through the shield grounded at both ends. To rectify the
problem, do not, under any circumstances, open the shield of the bus cable.
Install an additional equipotential bonding conductor parallel to the bus cable to carry the
shield current.
• You can find additional information in the manual SIMATIC NET PROFIBUS Networks
(https://support.industry.siemens.com/cs/ww/en/view/1971286).
Wiring
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
Controllers
4.5 Relay and fieldbus interfaces
125

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sidoor atd420wSidoor atd410wSidoor atd430w

Table of Contents