Commissioning the control unit on PROFIBUS
We recommend the following initial commissioning procedure for a control unit as DP slave
on PROFIBUS DP:
Table 9- 3
Step
1
2
3
4
5
6
7
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
Procedure for commissioning the control unit as a DP slave on PROFIBUS DP
Procedure
Commission the control unit without a fieldbus connec-
tion as described in the previous sections.
Configure the DP master (including PROFIBUS ad-
dress)
Switch on supply voltage for DP master
Switch on supply voltage for control unit (DP slave)
Load the configuration in the DP master
Switch DP master to RUN mode
Controlling LEDs on the control unit
Connecting and commissioning
9.6 Commissioning the control unit on the fieldbus
See...
Sections Preparing the con-
trol unit (Page 263) to Con-
necting digital inputs
(Page 267)
Documentation of the DP
master
Documentation of the DP
master
Connecting the power supply
to the network and executing
a learn run (Page 266) sec-
tion
Online help of the configura-
tion tool, e.g. STEP 7
Documentation of the DP
master
Final settings and checks
(Page 271) section