Siemens SIDOOR ATD401W System Manual page 115

Atd4xxw series, door control systems for industrial applications
Hide thumbs Also See for SIDOOR ATD401W:
Table of Contents

Advertisement

Cable ties (strain relief in housing)
Cable ties (security against being pulled out within the protective cover)
Minimum length of the cable jacket within the protective cover: 5 mm
Minimum length of the single-insulation on the single cores: 5 mm
Insertion direction for the protective cover
1. Unscrew the fixing screw holding the protective cover on the relay module.
2. Slide the protective cover against the insertion direction and remove it.
3. Connect connectors X11, X12 and X13.
4. Ensure that, inside the cover, the single-insulation is removed from the single cores at
least 5 mm from the cable entry openings, and the cores connected to the terminal
connectors are as short as possible.
5. Secure the cables inside the plastic cover against being pulled out through the oval
aperture in the relay cover. Use cable ties for this purpose, tie each of them tightly round
the cable.
Ensure that the cable tie is tied so that at least 5 mm of the outer cable jacket lies inside
the protective cover.
6. Provide additional strain relief by attaching more cable ties to the fixing points provided in
the housing.
7. Slide the protective cover in the insertion direction back into its correct position.
8. Screw the fixing screw holding the protective cover on the relay module back in.
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
Controllers
4.5 Relay and fieldbus interfaces
115

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sidoor atd420wSidoor atd410wSidoor atd430w

Table of Contents