4.5 Relay and fieldbus interfaces
DIP switches (S501)
The DIP switches (S501) on the device are used to set the PROFIBUS address of the DP
slave.
Status: 1≙ on
Status: 0 ≙ off
DIP switch without function
DIP switches for setting the address
Figure 4-2
Setting the address
The individual DIP switches 1 to 7 (
reserved.
Addresses within the range from 0 to 127 can be set with combinations of the seven DIP
switches (
Decimal).
Note
A DP slave address change only becomes effective after a power-on reset or system restart.
The following example shows the setting for the address "89":
DIP switches
Status
(0 ≙ off / 1≙ on)
Address
124
DIP switches (S501)
,
). The addresses are coded according to BCD code (Binary Coded
1
1
) are used to specify the address. DIP switch 8 (
2
3
4
0
0
1
89 (≙ 59
ATD4xxW Door Controller for Industrial Applications