10.1.2 Communication Cassette Specifications

 RS-232C / RS-485 interface
Items
AFP0HCCS1
RS-232C × 1 ch
Interface
(non-insulated)
(Note 1)
Transmission
RS-232C: Max. 15 m (Note 3)
distance
RS-485: Max. 1200 m (Note 4) (Note 5)
Baud rate
4800, 9600, 19200, 38400, 57600, 115200, 230400 bit/s
Communication
Half-duplex transmission
method
Synchronous
Start stop synchronous system
method
Communication
Data length: 7 bits / 8 bits; Stop bit: 1 bit / 2 bits; Parity: None / Odd / Even;
format
Header: STX / No STX; Terminator: CR / CR+LF / None / ETX / Time (0 to 100 ms)
Data transmission
Transmits from bit 0 character by character.
order
PLC link: Max. 16 units
Communication
MEWTOCOL-COM (master / slave): Max. 99 units
functions and the
MODBUS RTU (master / slave): Max. 99 units
number of
General-purpose communication: Max. 99 units
connected units
Modem initialization
(Note 1): AFP0HCCS1 is a 5-wire type. When using it as a 3-wire type, short-circuit the RS-CS terminals.
(Note 2): When connecting a commercially available device that has an RS-485 interface, please confirm operation
using an actual device. In some cases, the number of units, transmission distance, and baud rate vary
depending on the connected device.
(Note 3): When communication is performed at a baud rate of 38400 bit/s or higher, use a cable not longer than 3 m.
When wiring RS-232C, a shielded wire must be used to increase noise suppression.
(Note 4): The transmission distance is limited as follows by the baud rate and the number of connected units when
setting RS-485. For the baud rate of 38400 bit/s or lower, the max. distance is 1200 m, and the max. number
of connected units is 99. When using in combination with a C-NET adapter, the max. number of connected
units is limited to 32, and the baud rate is limited to 19200 bit/s or lower.
When baud rate is set to 230.4 kbps
99
70
Number
of units
40
20
0
200
Transmission distance (m)
(Note 5): For an RS-485 converter on the PC side, SI-35 from Lineeye Co., Ltd. is recommendable.
AFP0HCCS2
RS-232C (3-wire type) ×
2 ch (non-insulated)
When baud rate is set to 115.2 kbps
When baud rate is set to 57.6 kbps
700
1000 1200
10.1 Communication Function Specifications
Description
AFP0HCCM1
RS-485 × 1 ch
(insulated)
(Note 2)
AFP0HCCS1M1
RS-485 × 1ch (insulated)
RS-232C (3-wire type) ×
1ch (non-insulated)
(Note 2)
10-3