Panasonic FP0H User Manual page 51

Programmable controller
Hide thumbs Also See for FP0H:
Table of Contents

Advertisement

Description
Code
Number of transfer
words
COM port number of a
master unit
Unit number of a
destination unit
Memory area to store
control data
SEND / RECV
executable flag
Memory area of a
master unit that stores
send data;
Destination unit send
data storage area
(Note): For details of instruction programming, refer to 8.2.2 [F145 SEND] Data Transmission (MEWTOCOL-COM
Master).
KEY POINTS
Other F145 (SEND) / F146 (RECV) instructions cannot be executed at the
same time to a communication port during master communication. Confirm
that the "SEND / RECV instruction executable flag" is ON, and execute the
instructions.
F145 (SEND) / F146 (RECV) instruction cannot be executed at the same time
to a port during slave communication.
The processing of F145 (SEND) / F146 (RECV) instruction is handled during
the execution of ED instruction. Check the SEND / RECV done flag to
confirm the completion of transmission / reception. Tuened ON in the case
of an error, and an error code is stored in DT90123-DT90125.
In the case of COM0 port, specify "HF" as a COM port No. for an operand of
the F145 (SEND) / F146 (RECV) instruction.
 Special relays / special data registers
SEND / RECV executable flag
SEND / RECV done flag
SEND / RECV done code
(Note): The Nos. in brackets indicate devices that are compatible with existing FP-X / FPΣ.
5.3 MEWTOCOL-COM Master Communication (SEND)
Specify the number of words in higher words of control data.
Range: H1 to H1FB (1 word to 507 words)
Specify a COM port No. for the higher 4 bits in lower words of control data.
HF: COM0 port; H1: COM1 port; H2: COM2 port
Specify a unit number of a destination unit for the lower 8 bits in lower words of
control data.
Range: H00 to H63 (K0 to K99)
Specify the starting number of the area (2 words) that specifies the transfer
method and the number of transfer data.
This is inserted to confirm that no SEND / RECV instruction is in progress for
the same port. Turns ON when an instruction is executable.
Specify the memory area of a master unit that stores send data.
Using two operands, specify the type and relative address of the memory area
of a destination unit that stores send data.
COM0
R9134
R9135
DT90123
COM1
COM2
R913C (R9044)
R9144 (R904A)
R913D (R9045)
R9145 (R904B)
DT90124
DT90125
5-7

Advertisement

Table of Contents
loading

Table of Contents