Panasonic FP0H User Manual page 103

Programmable controller
Hide thumbs Also See for FP0H:
Table of Contents

Advertisement

Name
No.
410
Unit number
411
Communication mode
412
Selection of modem
connection
413
Transmission format
414
415
Setting of baud rate
(COM1) Receive buffer
starting number in
416
general-purpose
communication
(COM1) Receive buffer
capacity in general-
417
purpose communication
(COM2) Receive buffer
starting number in
418
general-purpose
communication
(COM2) Receive buffer
capacity in general-
419
purpose communication
(COM0) Receive buffer
starting number in
420
general-purpose
communication
(COM0) Receive buffer
421
capacity in general-
purpose communication
(COM0)
Terminator judgment
424
time (x 0.01 ms)
(COM1)
425
Terminator judgment
time (x 0.01 ms)
(COM2)
426
Terminator judgment
time (x 0.01 ms)
(Note 1): The range of system register Nos. 416 / 418 / 420 varies depending on the value of the system register No.0
as below.
System register No.0
Setting of sequence program
area capacity
24Kstep
32Kstep
40Kstep
64Kste
Default
1
1 to 99
Computer link
General-purpose communication
Computer link
PLC link
MODBUS RTU
No
Yes / No
Data length:
Data length 7 bits / 8 bits
8 bits
Parity check: None / Odd / Even
Parity check:
Stop bit: 1 bit / 2 bits
Odd
Terminator selection: Code / Time
Stop bit:
Terminator: CR / CR+LF / None / EXT
1 bits
Hader: No STX / STX
4800 bps, 9600 bps, 19200 bps, 38400 bps, 57600
9600 bps
bps, 115200 bps, 230400 bps
0
0 to 65532 (Note 1)
2048
0 to 2048
2048
0 to 65532 (Note 1)
2048
0 to 2048
4096
0 to 65532 (Note 1)
2048
0 to 2048
0
0 or 1 to 10000 (0.01 ms to 100 ms)
0
When 0 is specified, transmission time is that for
approx. 4 bytes.
0
System register Nos. 416 / 418 / 420 / 422
Receive buffer starting address during general-purpose
communication
0 to 65532
0 to 32764
0 to 24572
0 to 12284
10.2 List of System Data Registers
Setting range and description
10-9