10.2 List of System Data Registers

No.
Name
Setting of sequence program area
0
capacity (Note 1) (Note 3)
1
Internal relay capacity (Note 1)
5
Counter starting No.
Hold type area starting No. for timer
6
/ counter
Hold type area starting No. for an
7
internal relay
(Note 2)
Hold type area starting No. for a
8
data register
(Note 2)
Hold / non-hold selection for a
14
stepladder
Hold / non-hold of a previous value
4
in the leading edge detection of the
DF instruction during MC
PLC link W0-0 link relay
10
hold-type area starting word No.
PLC link W0-1 link relay
11
hold-type area starting word No.
PLC link W0-0 link register
12
hold-type area starting No.
PLC link W0-1 link register
13
hold-type area starting No.
Selection of duplicate output
20
(disable / enable)
Selection of operation mode (stop /
23
run) in case of I / O verification error
Selection of operation stop (stop /
run) in the case of configuration data
24
error / initialization request error
(only for types with built-in Ethernet
functions)
Selection of operation mode (stop /
25
run) in case of positioning operation
error
Selection of operation mode (stop /
26
run) in case of operation error
Selection of operation mode (stop /
run) in case of network error (only
27
for types with built-in Ethernet
functions)
10-4
Default
Setting range and description
C32: 24, 32 k words
32
C32E: 24, 32, 40, 64 k words
C32: 4096, 8192
8192
C32E: 8192 (fixed)
1008
0 to 1024
1008
0 to 1024
248
0 to 256
504
0 to 512
C32:
32450
0 to 32765
65218
0 to 65533
C32E:
11970
0 to 12285
24258
0 to 24573
32450
0 to 32765
65218
0 to 65533
Non-hold
Hold / non-hold
Hold
Hold / non-hold
64
0 to 64
128
64 to 128
128
0 to 128
256
128 to 256
Disable
Disable / enable
Stop
Stop / run
Stop
Stop / run
Run
Stop / run
Stop
Stop / run
Stop
Stop / run