2.4.4 AFP0HCCS1M1 (RS-485 1ch insulated + RS-232C 1ch Non-Insulated
Type)
Setting of cassette backside switch
A termination resistance selector switch for RS-485 interface is located on communication
cassette AFP0HCCS1M1. Turn ON this switch only when it is the end unit. An equivalent
circuit diagram is indicated below.
SW
Terminal layout
+
SD RD SG
Terminal
Allocated function
code
+
Transmission line (+)
-
Transmission line (-)
SD
Send Data
RD
Receive data
SG
Signal Ground
Example of wiring
AFP0HCCS1M1
Pin name
Signal name
Transmission line (+)
+
Transmission line (-)
-
SD
Send data
RD
Receive data
SG
Signal ground
2.4 Wiring of COM Port of a Communication Cassette
+
Signal direction
-
-
PLC → External device
PLC ← External device
-
Abbr.
+
ー
SD
RD
SG
Port allocated on the
LED
software
S1
COM1
R1
S2
R2
COM2
-
Connection destination 1
Code
Signal name
Transmission line (+)
+
Transmission line (-)
-
(To another device)
Connection destination 2
Code
RD
SD
SG
Signal name
Receive data
Send data
Signal ground
2-11