8.2.7 [F146 RECV] Data Reception (MODBUS Master)

 Instruction format
R0
 Devices that can be specified (indicated by ●)
Operand
WX
WY
s
S1
S2
n
D
(*1): A character constant cannot be specified.
 Operands
Operands
Settings
Specify the starting number of the area (2 words) that stores control data.
S1
S1
S1+1
Specification of
S2
a destination unit
Specification of
n
a destination unit
Specification of
D
a master unit
(Note 1): To [S1], the following specification should be applied. The specification method differs depending on word
transfer and bit transfer.
[S1]:
H0
Transfer in
Specify the number of send words
word units
H001 to H07F (1 to 127 words)
[S1]:
H8
Transfer in
Master unit bit No.
bit units
(H0 to HF)
(Note 2): To [S1+1], the following specification should be applied. When the COM port No. is 0, specify HF for the
highest digit.
[S1+1]:
H0 (fixed)
Select a COM port
(H1/H2/HF)
8-14
F146 RECV
WR
WL
SV
EV
Specify the transfer method.
Word transfer: Specify the number of send words.
Bit transfer: Specify the bit number of a master unit and that of a
destination unit.
Specify the COM port No. of a master unit and the unit number of a
destination unit.
Specify the source data area of a destination unit. (Device
No. is fixed to "0")
Specify the starting address of the device in the source
data area of a destination unit.
Specify the device starting address of the receive data
storage area in the master unit.
H0 (fixed)
Destination bit No.
(H0 to HF)
Unit No. (H00 to H63)
(0 to 99)
DT10
DT0
K100
S1
S2
DT
LD
In
SWR SDT
DT50
n
D
Constant
Index
modifier
K
H
(*1)
Remark
(Note 1)
(Note 3)
(Note 2)
(Note 4)
(Note 4)
(Note 3)