5 Installation

5 Installation
5.1

Place of Installation

The conditions listed below must be met before installing the DX200:
• Non-Hazardous area
• Ambient temperature must be 0 to 45° C (32 to 113°F) during operation
and -10 to 60°C (14 to 140°F) during transportation and maintenance.
• Humidity must be low with no condensation (10~90%RH).
• It must be a place with little dirt, dust, or water.
• No flammable or corrosive liquids or gases, etc. in the area.
• Little jarring or potential for striking of the DX200 (under 0.5G oscillation).
• No large electric noise source nearby.
• No potential for collision with moving equipment such as forklifts.
If the external electric noise applies, the alarm occurs and the
manipulator may stop.
When the alarm occurs and the manipulator stops, refer to
DX200 maintenance manual and reset the alarm.
Devices that are not explosion proof must not be installed in hazardous area.
Failure to observe this warning may result in a fire.
WARNING
5-1
174117-1CD
.
HW1483325
17/33