2. Use the UP/DOWN arrow keys to locate the
desired permanent hold type (or resume
schedule). Press YES to enter the choice.
3. Press YES to return to the Status Display Menu
or NO to change the schedule hold selection
again.
Accessories
Using the information in Table 9, contact the nearest
Johnson Controls® branch office or wholesale
distributor to order these accessories.

Technical Specifications

Product
Power Requirements
Relay Contact Rating
Maximum Inductive
Digital Inputs
Economizer Output
Recommended Wire Size
Thermostat Measurement
Range
Sensor Type:
Resolution:
Control Accuracy
Outdoor Air Temperature
Indication Range
Setpoint Control Range
Minimum Deadband
Ambient Operating
Conditions
Ambient Storage
Conditions
Dimensions (H x W x D)
Shipping Weight
UL and cUL Listing
FCC Compliance
Industry Canada
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201
18
T600MEP-2 Programmable Economizer Thermostat Installation Instructions
T600MEP-2 Programmable Economizer Thermostat
20-30 VAC, 50/60 Hz, 24 VAC nominal, Class 2 or Safety Extra Low Voltage (SELV)
1 ampere with in-rush surges up to 3 amperes, 30 VAC maximum, Class 2
Relay dry contact only across the C terminal to DI1 or DI2
0 to 10 VDC into 2 K ohm resistance minimum
18 gauge maximum, 22 gauge recommended
-40 to 122°F (-40 to 50°C)
Local 10 K ohm NTC thermistor
±0.2F° (±0.1C°)
±0.9F° (±0.5C°) @ 70°F (21°C) typical calibrated
-40 to 50°C (-40 to 122°F)
Cooling: 54 to 100°F (12 to 37.5°C) in 1/2 degree increments
Heating: 40 to 90°F (4.5 to 32°C) in 1/2 degree increments
(Between heating and cooling) 2F° or 1C°
32 to 122°F (0 to 50°C); 0 to 95% RH noncondensing
-22 to 122°F (-30 to 50°C); 0% to 95% RH noncondensing
4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
0.75 lb (0.34 kg)
File E27734 with CCN's XAPX (US, UL 873) and XAPX7 (Canada, CSA C22.2 No. 24)
This equipment has been tested and found to comply with the limits for a Class A digital
device and verified to Class B pursuant tos Part 15 of FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when this
equipment is operated in a commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area is likely to cause harmful interference, in which case the
user will be required to correct the interference at his/her own expense.
This Class A digital apparatus meets all of the requirements of the Canadian Interference-
Causing Equipment Regulations. Cet appareil numérique de la Classe A respecte toutes
les exigences du Règlement sur le materiél brouilleur du Canada.
Table 9: Optional Accessories
(Includes Mounting Hardware)
Item
Remote Indoor Temperature Sensor
Outdoor Air Temperature Sensor
Duct Mount Temperature Sensor
Remote Indoor Temperature Sensor
with Occupancy Override and LED
Product Code
Number
SEN-600-1
SEN-600-2
SEN-600-3
SEN-600-4
Printed in U.S.A.