Johnson Controls T600MEP-2 Installation Instructions Manual page 6

Programmable economizer thermostat

Advertisement

Table 1: Installer Configuration Menu (Cont.)
Sets the Duration for Temporary
TOccTime
Occupancy Time
set? Y/N
Default: Three Hours (3.0 hrs)
See the Establishing the Temporary
Occupancy Time (TOccTime) section.
Room Air Sensor Calibration (Offset)
Cal RS
Default: 0.0°F (0.0°C)
set? Y/N
See the Room Air Sensor Calibration
(Cal RS) section.
Outdoor Air Sensor Calibration (Offset)
Cal OS
Default: 0.0°F (0.0°C)
set? Y/N
See the Outdoor Air Sensor
Calibration (Cal OS) section.
Enable/Disable Second Heating Stage
H Stage
Default: Two Stages
set? Y/N
See the Enable/Disable Second
Heating Stage (H Stage) section.
Enable/Disable Second Cooling Stage
C Stage
Default: Two Stages
set? Y/N
See the Enable/Disable Second
Cooling Stage (C Stage) section.
Disables Heating Operation based on
Outdoor Air Temperature
H lock
Default: 120°F (49°C)
set? Y/N
See the Setting the Heating Lockout
(H lock) section.
Disables Cooling Operation based on
Outdoor Air Temperature
C lock
Default: -40°F (-40°C)
set? Y/N
See the Setting the Cooling Lockout
(C lock) section.
Sets the Number of Events in 24-Hour
2/4event
Period
set? Y/N
Default: Two Events (2.0)
See the Selecting the Number of
Events (2/4event) section.
Sets the Auxiliary Contact as Normally
Open or Normally Closed
Aux cont
Default: Normally Open (N.O.)
set? Y/N
See the Configuring the Auxiliary
Contact (Aux cont) section.
Enable/Disable Progressive Recovery
Prog Rec
Default: Off
set? Y/N
See the Enable/Disable Progressive
Recovery (Prog Rec) section.
Sets the Economizer Changeover
Temperature
Chngstpt
Default: 55°F (13°C)
set? Y/N
See the Setting the Economizer
Changeover Temperature (Chngstpt)
section.
6
T600MEP-2 Programmable Economizer Thermostat Installation Instructions
Sets the Outdoor Air Damper Minimum
Position
Min pos
Default: 0%
set? Y/N
See the Setting the Outdoor Air
Damper Minimum Position (Min pos).
section.
Sets the Mechanical Cooling Mode
C mech
Default: Off
set? Y/N
See the Setting the Mechanical
Cooling Mode (C mech) section.
Sets the Mixed Air Temperature
Setpoint
Mix stpt
Default: 55°F (13°C)
set? Y/N
See the Setting the Mixed Air
Temperature Setpoint (Mix stpt)
section.
Displays the Mixed Air Temperature
Display
Default: None
MS? Y/N
See the Displaying the Mixed Air
Temperature (Display) section.
Configuring the Digital Inputs (DI1 and DI2)
Press the configuration menu access key. The first
prompt is to program Digital Inputs DI1 and DI2.
The digital inputs display an alarm condition when the
input is closed. An alarm message is included on the
scrolling Status Display Menu and when the message
is displayed, the backlight momentarily lights up.
Each digital input can be programmed in one of five
conditions.
None – No function is associated with the input.
Service – A Service alarm is displayed.
Filter – A Filter alarm is displayed.
RemNSB – Remote Night Setback (NSB) timer
clock input. The scheduling is set per the digital
input when this option is selected. The time
continues to be displayed, but the menu related to
scheduling is disabled and no longer accessible.
Open Contact = Occupied setpoints
Closed Contacts = Unoccupied setpoints
RemOVR – Remote override contact. This
disables all override menu functions of the
thermostat. The override function is controlled
manually by a remote, momentarily closed
contact. When configured in this mode, the input
operates in a toggle mode. With this function
enabled, it is now possible to toggle between
unoccupied and occupied setpoints for the amount
of time set by the temporary occupancy time
parameter.