Download Print this page

Johnson Controls T600MEP-2 Installation Instructions Manual page 3

Programmable economizer thermostat

Advertisement

Terminal
Y1
Energizes on a call for first stage cooling
Y2
Energizes on a call for second stage cooling
G
Energizes fan in accordance with the selected fan mode
RC
24 VAC from equipment transformer
C
24 VAC (common) from equipment transformer
RH
24 VAC for heating stages
W1
Energizes on a call for first stage heating
W2
Energizes on a call for second stage heating
AUX
Configurable auxiliary output
D1
Configurable digital input
D2
Configurable digital input
RS
Remote room sensor
Scom
Sensor common
OS
Outdoor air sensor
MS
Mixed air sensor
EC
0 - 10 VDC Economizer actuator output
Y2
Y1
G
RC
Cool 1
Cool 2
Cool 2
Fan
24 VAC
Thermostat Power
Function
RH
W1
W2
C
Heat 1 Heat 2
If using the same power source
for the thermostat and heating
loads, install a jumper
across RC and RH.
Figure 5: T600MEP-2 Thermostat Wiring Schematic
T600MEP-2 Programmable Economizer Thermostat Installation Instructions
5 pole left top connector
Y1
Y2
8 pole bottom connector
EC AUX
AUX
D2
RS
D1
EC
Aux
Remote
Room
Sensor
3 pole right top
connector
C
G
RC
RH W1 W2
D1 D2
RS
MS
OS
Scom
Scom
OS
Remote
Remote
Outdoor
Mixed Air
Sensor
Sensor
3