Chapter 4 Parameters|
AO1 Terminal Analog Signal Mode
12.20
Settings
Besides parameter setting, the voltage/current mode should be used with the switch.
AO1 Analog Output Signal
12.21
Settings
This parameter is used to choose analog frequency (0-+10Vdc) or analog current (4-20mA) to
correspond to the AC motor drive's output frequency or current.
AO1 Analog Output Gain
12.22
Settings
This parameter is used to set the analog output voltage range.
When Pr.12.21 is set to 0, analog output voltage corresponds to the AC motor drive's output
frequency. When Pr.12.22 is set to 100, the max. output frequency (Pr.01.00) setting
corresponds to the AFM output (+10VDC or 20mA)
When Pr.12.21 is set to 1, analog output voltage corresponds to the AC motor drive's output
current. When Pr.12.22 is set to 100, the 2.5 X rated current corresponds to the AFM output
(+10VDC or 20mA)
4-134
0
AVO1
1
ACO1 (analog current 0.0 to 20.0mA)
2
ACO1 (analog current 4.0 to 20.0mA)
AVI3
AVI4
ACI2
ACI3
0
Analog Frequency
1
Analog Current (0 to 250% rated current)
1 to 200%
AVO1
AVO2
ACO1
ACO2
Revision November 2007, 03EE, SW--PW V1.10/CTL V2.10
Factory Setting: 0
Factory Setting: 0
Unit: 1
Factory Setting: 100