Inspecting And Unpacking Each Cabinet; Figure 1---1. Cabinets As Shipped, With Outer Packaging And Pallet - Powerware 9315s Installation & Operation Manual

Parallel capacity/redundant ups with powerhandler plus switchboard system bypass module (ssbm)
Table of Contents

Advertisement

1.1.5

Inspecting and Unpacking Each Cabinet

NOTE: Refer to the applicable Powerware 9315 Installation manual provided with
the UPMs for UPM unpacking instructions.
The first task in preparing for installation is inspecting and unpacking the SSBM.
The SSBM is shipped in sections which are bolted to wooden pallets and protected
with outer protective packaging material as shown in Figure 1---1 and a plastic inner
covering.

Figure 1---1. Cabinets as Shipped, with Outer Packaging and Pallet

1.
Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION:
Do not install a damaged cabinet. Report any damage to the carrier and
contact your local sales or service office immediately.
CAUTION:
Only insert the forklift jacks where "FORK HERE" signs appear on cabinet
packaging.
2.
Use a forklift or other material handling equipment to move the cabinet to a
convenient unpacking area. Insert the forklift jacks between the raised
supports on the bottom of the pallet.
CAUTION:
Do not tilt cabinets more than 10 degrees from vertical.
3.
Set each pallet on a firm, level surface, allowing a minimum clearance of
4.6m (15 ft) on each side for removing the cabinets from the pallets.
1--4
OUTER
PACKAGING
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
WOODEN
PALLET
164201373 Rev. A
092402