Using The Lcd Screen 9; Figure 9---2. Parts Of The Lcd Screen - Powerware 9315s Installation & Operation Manual

Parallel capacity/redundant ups with powerhandler plus switchboard system bypass module (ssbm)
Table of Contents

Advertisement

Using the LCD Screen
9.2
The LCD screen at the top of the Control Panel provides an operator interface with
the Parallel Capacity/Redundant system. Figure 9---2 identifies the display fields
discussed in the following sections.
A
System Normal
ALARM:
NONE
NOTICES: NONE
B
Battery
Minutes
48.6
C
Meters
D
System
Load Amps
Versions
E
Meters
Events Statistics Graphics
A
The UPS status area contains three lines that display the current state of the UPS. The first
line shows the present operational mode of the UPS. The second line shows the highest level
of the current active alarms, and the third line shows any notices the UPS has posted. (For
more information about alarms and notices, refer to Chapter 12, "Responding to System
Events.")
B
The battery charge box shows the minutes of battery capacity available.
C
The menu box shows the currently selected menu and lists the options available on that
menu. The title at the top of the menu box is also shown below on the menu bar (E). Press
the
and
D
The currently selected option is highlighted in the menu box. Press the
to move the highlight up or down. The data in the information area (G) changes accordingly.
E
The menu bar lists the titles of the menus. The title of the menu currently displayed in the
menu box is highlighted. When you press the
left or right, the data in the menu box and the information area change accordingly.
9--2
Uninterruptible Power System
Input
VAB
VBC
480
480
IA
480
480
KVA
399
379
Bypass
VAB
VBC
480
480

Figure 9---2. Parts of the LCD Screen

(Typical for Powerware 9315---300 480/480V Unit)
pushbuttons to scroll up and down through the options in the menu box.
VCA
FREQ
VAB
480
60.0
480
IB
IC
IA
480
361
KW
PF
0.95
VCA
480
Setup
and
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
15 JUL 1998
09:25:42
Output
VBC
VCA
FREQ
480
480
60.0
IB
IC
IN
361
361
000
KVA
KW
PF
300
240
0.80
Battery
V
I
+
540
18
and
pushbuttons to move the highlight
164201373 Rev. A
F
G
pushbuttons
092402

Advertisement

Table of Contents
loading