Using The Menu Options 9; System Meters Screen 9; Figure 9---3. System Meters Screen - Powerware 9315s Installation & Operation Manual

Parallel capacity/redundant ups with powerhandler plus switchboard system bypass module (ssbm)
Table of Contents

Advertisement

Using the Menu Options
9.6
The UPS menus allow you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are
available:
Meters
Events
Statistics
Graphics
Setup
9.6.1
System Meters Screen
Figure 9---3 shows the LCD screen as it appears when you first start the UPS. The
Meters menu is displayed in the menu box, with the System option highlighted. In the
information area, the system meters show their current readings.
System Normal
ALARM:
NOTICES: NONE
Battery
Minutes
Meters
System
Load Amps
Versions
Meters
The Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the KVA, KW, and power factor measurements. The output
area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I).
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
Displays performance meters for the system or critical load.
Displays the list of Active System Events and a historical log of
system events.
Displays statistical information about UPS operations for the
battery, load, or line.
Displays a real-time graphic representation of the flow of current
through the internal UPS components.
Allows you to configure the UPS communications port and set
the date and time for the time stamp.
Uninterruptible Power System
NONE
48.5
VAB
480
IA
480
KVA
399
VAB
480
Events Statistics Graphics Setup

Figure 9---3. System Meters Screen

(Typical for Powerware 9315---300 480/480V Unit)
Input
VBC
VCA
FREQ
480
480
60.0
IB
IC
480
480
KW
PF
379
0.95
Bypass
VBC
VCA
480
480
15 JUL 1998
09:25:42
Output
VAB
VBC
VCA
FREQ
480
480
480
60.0
IA
IB
IC
IN
361
361
361
000
KVA
KW
PF
300
240
0.80
Battery
V
I
540
+
18
9--5