Safety Output Parameter Groups - Omron DST1-ID12SL-1 Operation Manual

Dst1 series safety i/o terminals
Hide thumbs Also See for DST1-ID12SL-1:
Table of Contents

Advertisement

Editing Parameters
3-1-6

Safety Output Parameter Groups

Item
S
Safety Output Channel
Mode
S
Dual Channel Safety
Output Mode
I/O Comment
Maintenance Counter
Mode Choice
Threshold Mainte-
nance Counter
This section describes parameters in the safety output groups.
The safety output parameters are grouped by terminal number.
Settings
Not Used.
The safety output is not used. (External out-
put device not connected.)
Safety
Specifies not outputting the test pulse when
the output is ON. Contact between the out-
put signal line and the power supply (posi-
tive) when the output is OFF and ground
faults can be detected.
Safety Pulse Test
Outputs the test pulse when the output is
ON.
(Setting supported only
for the DST1-MD16SL-
Contact between the output signal line and
1.)
the power supply, and short circuits with
other output signal lines can be detected.
Single Channel
Specifies using Single Channel Mode.
When Single Channel is set, the safety out-
put that would be paired for the dual channel
parameter is also set to Single Channel
Mode.
Dual Channel
Specifies using Dual Channel Mode.
When both of the safety outputs to be paired
are normal, the outputs can be turned ON.
32 characters max.
Sets an I/O comment for the safety output.
The I/O comment set here is used as the I/O
tag in the Logic Editor.
Time
Sets the operating mode for the mainte-
nance counter.
Count
0 to 4,294,967,295
Sets the threshold value for the maintenance
hours
counter.
Description
Section 3-1
Default
Not Used.
Dual Channel
None
Time
0