Test Output Parameter Groups - Omron DST1-ID12SL-1 Operation Manual

Dst1 series safety i/o terminals
Hide thumbs Also See for DST1-ID12SL-1:
Table of Contents

Advertisement

Editing Parameters
3-1-5

Test Output Parameter Groups

Item
S
Test Output Mode
Fault Action
I/O Comment
Maintenance Counter
Mode Choice
Threshold Mainte-
nance Counter
Note
64
This section describes parameters in the test output groups.
The test output parameters are grouped by terminal number.
Settings
Not Used.
The corresponding test output is not used.
Standard Output
Specifies connecting to the input for a muting
lamp or PLC. Used as a monitor output.
Pulse Test Output
Specifies connecting a device with a contact
output in combination with the safety input.
Power Supply Output
Specifies connecting to the power supply ter-
minal of a safety sensor.
The voltages supplied to the IO power from
the test output are output.
Muting Lamp Output
Specifies a muting lamp output.
(Setting supported only
When the output is ON, disconnection of the
for T3 terminal.)
muting lamp can be detected.
Clear off
Sets the output state of the test output when
a communications error occurs.
Hold last data
This parameter is enabled when the Test
Output Channel Mode is set to Standard
Output or Muting Lamp Output.
32 characters max.
Sets an I/O comment for the test output. The
I/O comment set here is used as the I/O tag
in the Logic Editor.
Time (cumulative ON
Sets the operating mode for the mainte-
time monitor)
nance counter.
Count (contact opera-
tion counter)
0 to 4,294,967,295
Sets the threshold value for the maintenance
hours
counter.
The time and count maintenance counter modes (contact operation counter
and total ON time monitor function) cannot be used for the test output termi-
nals of the DST1-XD0808SL-1.
Description
Section 3-1
Default
Not Used.
Clear off
None
Time
0