9. Thread the RS485 communication cable through
the lock nut and the cable gland into the enclosure
of the Sunny SensorBox.
NOTICE
Metal or cable scraps could fall into the open device while working on the device.
Damage to the Sunny SensorBox will result.
• Remove all metal scraps from the cable shield or cable from inside the Sunny
SensorBox before closing the device.
5
10. Remove 1
 in. (40 mm) of cable sleeve from the
8
RS485 communication cable that is connected to
the Sunny SensorBox.
1
11. Strip
 in. (6 mm) of insulation from the wires.
4
12. Twist the cable shield into one string.
13. Pull the insulating tube over the cable shield. Allow 1
out of the insulating tube.
14. Insert the detached cable shield together with the
ground cable of the Sunny SensorBox into the
terminal.
Installation Manual
5
 in. (40 mm) of the cable shield to stick
8