S5-90U/S5-95U
3.4.2

Electrical Configuration of the S5-95U with External I/Os

Figures 3-27 and 3-28 show different configuration possibilities. Pay attention to the following points
when you design your configuration.
You must have a main switch (1) in accordance with VDE 0100 for your PLC, the sensors, and
the actuators.
You do not need an additional fuse (2) to connect your PLC and the load circuit to power if your
radial lines are a maximum of 3 meters (9.84 feet) long and are inherently earth-fault-proof and
short-circuit-proof.
You need a load power supply (3) for 24 V DC load circuits.
You need a back-up capacitor (rating: 200 µF per 1 A of load current) if you have non-stabilized
load power supplies.
You should ground the load circuit at one end.
ground conductor on the load power supply (terminal M) or on the isolating transformer.
You must provide earth-fault monitoring for any non-grounded load circuits.
You must separately fuse (5 and 6) the load voltage for sensor circuits and for actuator circuits.
You must connect the standard mounting rail of the S5-95U to the ground conductor through a
capacitor (7), (to suppress high-frequency noise) for non-grounded configurations.
You must have a low-resistance connection between the standard mounting rail and the
cabinet's chassis ground (9) for grounded configurations.
You need a power fuse (8) to protect against a short-circuit occurring in the power supply.
EWA 4NEB 812 6115-02b
Installation Guidelines
Provide a removable connection (4) to the
3-27