Siemens SIMATIC S5-90U System Manual page 466

Table of Contents

Advertisement

Module Spectrum
Connection of the Module
Figure 15-22 shows how to connect loads to the voltage outputs of the module.
The sensor lines (S+ and S-) must be directly connected to the load, so that the voltage is
measured and regulated directly at the load. In this manner, voltage drops of up to 3 V per line can
be compensated for.
The sensor lines can be left out if the resistances of the QV and M lines are negligible compared to
the load resistance. In such a case, connect terminal S + to terminal QV, and terminal S to M
1
+
L
M
DC 24 V
(4/8)
(3/7)
QV
S+
R
L
Figure 15-22. Load Connection via a Four-Wire Circuit (6ES5 470-8MD12)
Analog Value Representation
Table 15-37. Analog Output Module 470-8MD12 (Unipolar)
Units
Output Values
in V
1280
6.0
1025
5.004
1024
5.0
512
3.0
1
1.004
0
1.0
- 1
- 0.996
- 256
0.0
- 512
- 1.0
- 1024
- 3.0
- 1280
- 4.0
15-100
S+
S-
S+
3
5
7
QV
M
QV
ANA
2
4
6
8
(5/9)
(6/10)
Terminal assignment
S-
M
Terminals
ANA
High Byte
0
1
0
1
0
0
0
1
0
0
0
0
0 1 0 0 0 0 0 0 0 0 0 0 x x x x
0 0 1 0 0 0 0 0 0 0 0 0 x x x x
0 0 0 0 0 0 0 0 0 0 0 1 x x x x
0 0 0 0 0 0 0 0 0 0 0 0 x x x x
1 1 1 1 1 1 1 1 1 1 1 1 x x x x
1 1 1 1 0 0 0 0 0 0 0 0 x x x x
1 1 0 0 0 0 0 0 0 0 0 0 x x x x
1 1 0 0 0 0 0 0 0 0 0 0 x x x x
1 0 1 1 0 0 0 0 0 0 0 0 x x x x
S-
Key:
9
QV:
M
ANA
S±:
M
:
ANA
10
R
:
L
Low Byte
0
0
0
0
0
0
x
x
x
x
0
0
0
0
0
1
x
x
x
x
S5-90U/S5-95U
.
ANA
Analog output "Voltage"
Sensor line
Chassis ground terminal
of the analog unit
Load resistor
Range
Overrange
Nominal range
Overrange
EWA 4NEB 812 6115-02b