Siemens SIMATIC S5-90U System Manual page 423

Table of Contents

Advertisement

S5-90U/S5-95U
Table 15-16.
Analog Input Module 464-8MA21, 4x±50 mV with Linearization
and with Temperature Compensation (Internal); Thermoelement Type L
(Iron/Copper-Nickel (Konstantan), according to DIN 43710)
Thermal
Units
Voltage
in mV*
1361
901
900
53.14
500
27.85
250
13.75
100
+5.37
1
0.05
0
0
- 1
- 0.05
- 100
- 4.75
- 150
- 6.60
- 190
- 7.86
- 199
- 8.12
- 200
- 273
X
* For a reference temperature of 0° C (32° F)
** In the overrange, the current slope of the characteristic curve is maintained when leaving the linearized
nominal range.
Function block FB "polygon function" cannot be used, since linearization is executed by the
module.
EWA 4NEB 812 6115-02b
Tempe-
rature
High Byte
in °C
0 0 1 0 1 0 1 0 1 0 0 0 1 0 0 1
901
0 0 0 1 1 1 0 0 0 0 1 0 1 0 0 1
900
0 0 0 1 1 1 0 0 0 0 1 0 0 0 0 0
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
250
0 0 0 0 0 1 1 1 1 1 0 1 0 0 0 0
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
- 1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
- 100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
- 150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0
- 190
1 1 1 1 1 0 1 0 0 0 0 1 0 0 0 0
- 199
1 1 1 1 1 0 0 1 1 1 0 0 1 0 0 0
- 200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 1
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0 1
X
X X X X X X X X X X X X X 0 1 0
Module Spectrum
Low Byte
Range
Overflow
Overrange**
Nominal range
Overrange**
Overflow
Wire break
15-57