S5-90U/S5-95U
Analog Output Module 2 x±10 V
L+
1
M
2
QV
4
3
S+
Ch.0
S -
5
6
M ANA
QV
8
7
S+
Ch.1
S -
9
10
M ANA
R 3.3k
ANALOG OUTPUT
2 x± 10 V
6ES5 470-8MA12
1 2
3
4
5
6
0 V
- 15 V
+15 V
1
3
5
2
4
6
S+ QV
S- M A S+ QV S- M A
L+
M
Ch.0
EWA 4NEB 812 6115-02b
+
24 V
R
R
6
+9 V
GND
Data
7
9
10
Legend:
QV: Analog output
"voltage""
Ch.1
Technical specifications
Output range
(rated values)
Number of outputs
Galvanic isolation
Input resistance
min.
Capacitive load incl.
cable capacitance
Connection method
Digital representation
of output signal
Measured value
representation
Conversion time
(0 to 100%)
max.
Permissible overload
Short-circuit protection
Short-circuit current
Permissible voltage
difference to ground
and between outputs
max.
Basic error limits
(operational error limits
at 25°C, referred to output
range of the module)
Operational error limits
(0 to 60 °C, referred to
output range)
(32 to 140 °F)
Length of cable
- shielded
max.
Supply voltage L+
(peripheral)
- rated value
- ripple V
PP
- permissible range
(ripple included)
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(Output to L +, between
outputs, output to + 9V)
- insulation group
- tested with
Current consumption
- from + 9 V (CPU)
typ.
- from L +
typ.
Power loss
of the module
typ.
Weight
approx.
Module Spectrum
(6ES5 470-8MA12)
±10 V
2
yes (outputs to
grounding point and
between outputs)
3.3 k
<100 nF
two- or four-wire
connection
11 bits + sign
(1024 units =
rated value)
two's complement
(left-justified)
0.15 ms
25%
yes
±30 mA
75 V DC/60 V AC
±0.3%
±0.6%
200 m (660 ft.)
24 V DC
3.6 V
20 to 30 V
12 V AC
1 x B
500 V AC
60 V AC
1 x B
500 V AC
120 mA
100 mA
3.1 W
220 g (10 oz.)
15-93

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s5-95u

Table of Contents