Module Spectrum
Function
The module 6ES5 464-8MC11 is suitable for connection of voltage sensors.
Wiring of the module (two-wire connection) is shown in the block diagram (on the first page of the
module description).
Start-Up of Module
Set the intended operating mode using the switch on the front panel of analog input modules 464-
8MC11. The switch is located on the right side at the top of the front panel of the module.
Power supply
Set the switch to the available power supply frequency. This selects the inte-
frequency:
gration time of the A/D converters for optimal interference voltage suppression.
Power frequency 50 Hz:
Power frequency 60 Hz:
Operation:
Set the number of channels you wish to assign on the input module. If there
are fewer than four channels, the measured values will be updated faster.
Broken wire:
Broken wire signalling not possible.
Table 15-19. Settings for the Operating Mode Switch for Analog Input Module 464-8MC11
Function
Power supply
frequency
Operation
No function
15-64
Integration time 20 ms
Integration time 16.66 ms
Settings for Operating Mode Switch
50 Hz
4
3
2
1
1 channel (ch.0)
2 chan. (ch.0 + ch1)
4
3
2
1
4
3
2
1
S5-90U/S5-95U
60 Hz
4
3
2
1
4 chan. (ch.0 to 3)
4
3
2
1
4
3
2
1
EWA 4NEB 812 6115-02b
4
3
2
1