Module Spectrum
Digital Output Module 4×24 V DC/0.5 A
L+
1
F
M
2
3
.0
.4
4
5
.1
.5
6
7
.2
.6
8
9
.3
.7
10
5
DIGITAL OUTPUT
4 x 24 V DC/0.5 A
6ES5 440-8MA12
1
2
3
4
5
6
1
3
5
2
4
6
L+
M
X.0
X.1
15-24
+9 V
GND
Data
7
9
8
10
X.2
X.3
Technical specifications
Number of outputs
Galvanic isolation
- in groups of
Load voltage L+
- rated value
- permissible range
(including ripple)
- value at t<0.5 s
Output current
for "1" signal
- rated value
- permissible range
- lamp load
max.
Residual current
at "0" signal
max.
Output voltage
- "1" signal
max.
Short-circuit protection
Fault LED (red)
Error diagnostics
Voltage induced on circuit
interruption (internal) limited to
Switching frequency
- resistive load
max.
- inductive load
max.
Total permissible
current of outputs
Driving of digital input
Paralleling of outputs
- maximum current
Length of cable
- unshielded
max.
Rated insulation voltage*
(+9 V to
)
- insulation group
Current consumption
- from +9 V (CPU)
typ.
- from L+(without load)
typ.
Power loss
of the module
typ.
Weight
approx.
* Relevant only for isolated assembly in the
ET 100U/200U
S5-90U/S5-95U
(6ES5 440-8MA12)
4
no
4
24 V DC
20 to 30 V
35 V
0.5 A
5 to 500 mA
5 W
0.5 mA
L+ (- 0.6 V)
short-circuit
protected output
with autom. switch
on when the short-
circuit does not exist
any more
short-circuit/no
load voltage L+
possible
- 15 V
100 Hz
2 Hz
2 A
possible
possible
0.8 A
100 m (330 ft.)
12 V AC
1×B
15 mA
25 mA
1.5 W
200 g (7 oz.)