Terminal assignment, connectors

WARNING
If the unit is incorrectly connected, this can result in damage or destruction.
The power cable or busbars must be mechanically fixed outside the unit.
Power unit
Terminal type:
600 A / 1000 A / 1200 A units
2000 A units
The units are designed for a permanent line supply connection in accordance with DIN VDE 0160, Section
6.5.2.1.
Protective conductor connection: Minimum cross-section 10 mm
The connection cross-sections should be determined according to the applicable regulations -
e.g. DIN VDE 100 Part 523, DIN VDE 0276 Part 1000.
The connection lengths should be determined according to the diagram in Chapter 6 – Connecting.
Function
Armature power input
Protective conductor PE
Armature circuit-motor connection
Pre-charging, main contactor / circuit breaker
Terminal strip WAGO 264-105
Conductor cross section
AWG
Stripped length
Function
Power connection,
pre-charging
Control circuit for
main contactor /
circuit breaker
38
ENGLISH
Through hole for M10 (Cu - busbar 3x25)
Through hole for M10 (Cu - busbar 5x40)
Terminal
1U1
1V1
1W1
1C1 (1D1)
1D1 (1C1)
max. 2.5 mm
max. 12
8 - 9 mm
Connection
Terminal
X_SCHÜTZ
1
2U1
2
2V1
3
2W1
4
5
SIMOREG DC-MASTER Converter Commutation Protector
2
. (Connection option, see Chapter 5.1)
Connection values/Comments
see Technical data, Chapter 3.2
2
Connection values/Comments
Cable cross-section 1.5 mm
Fuse protection 10 A (see Chapter 6.4)
Connection values the same as for the power unit
SIMOREG CCP (see above)
Wiring, main contactor/circuit breaker
(see the recommended connection in Chapter 6.2)
12.2010
2
Siemens AG
6RX1700-0DD74
Operating Instructions