Siemens SIMOREG DC-MASTER Operating Instructions Manual page 44

Converter commutation protector
Table of Contents

Advertisement

Commissioning
PNU
Description
U577
Voltage setpoint for the upper response threshold of the SIMOREG
(2577)
CCP chopper
The set voltage value defines the upper response threshold of the voltage
limiter implemented in the SIMOREG CCP. Within the scope of the turn-off
operation of the CCP, this limits the counter-voltage that occurs - which is
also necessary - when the armature current is reduced to a value that is not
dangerous for the basic unit and the associated SIMOREG CCP. The
required setting value depends on the blocking voltage strength of the
power semiconductors used in the basic converter (SIMOREG DC-
MASTER) and in the SIMOREG CCP and is therefore dependent on the
Unit MLFB.
The following table should be used to correctly set this parameter.
As a result of the unit MLFB for the basic converter and SIMOREG CCP,
two setting values are obtained from which the lower of the two should be
set at U577.
Example:
Basic converter MLFB: 6RA7085-6DV62-0 (r070=9) ⇒ U577=1300 V
SIMOREG CCP MLFB: 6RA7085-6FC00-0 (n570=250) ⇒ U577=1100 V
therefore the following setting is obtained: U577=1100 V
Table to determine the setting value for U577:
MLFB SIMOREG
DC-MASTER
6RA7013-6DV62-0
6RA7018-6DV62-0
6RA7025-6DV62-0
6RA7028-6DV62-0
6RA7031-6DV62-0
6RA7075-6DV62-0
6RA7078-6DV62-0
6RA7081-6DV62-0
6RA7085-6DV62-0
6RA7087-6DV62-0
6RA7091-6DV62-0
6RA7093-4DV62-0
6RA7095-4DV62-0
6RA7025-6GV62-0
6RA7031-6GV62-0
6RA7075-6GV62-0
6RA7081-6GV62-0
6RA7085-6GV62-0
6RA7087-6GV62-0
6RA7090-6GV62-0
6RA7093-4GV62-0
6RA7095-4GV62-0
6RA7086-6KV62-0
6RA7090-6KV62-0
6RA7093-4KV62-0
6RA7095-4KV62-0
6RA7088-6LV62-0
6RA7093-4LV62-0
6RA7095-4LV62-0
6RA7018-6DS22-0
6RA7025-6DS22-0
6RA7028-6DS22-0
6RA7031-6DS22-0
6RA7075-6DS22-0
6RA7078-6DS22-0
6RA7081-6DS22-0
6RA7085-6DS22-0
6RA7087-6DS22-0
6RA7091-6DS22-0
6RA7093-4DS22-0
6RA7095-4DS22-0
44
ENGLISH
[from SW 2.2 and higher]
MLFB
Setting value for U577 [V]
characteristic
number (r070)
1
1300
2
1300
3
1300
4
1300
5
1300
6
1300
7
1300
8
1300
9
1300
10
1300
11
1300
12
1500
13
1500
14
1700
15
1700
16
1700
17
1700
18
1700
19
1700
20
1700
21
1700
22
1700
23
2100
24
2100
25
2100
26
2100
27
2500
28
2500
29
2500
30
1300
31
1300
32
1300
33
1300
34
1300
35
1300
36
1300
37
1300
38
1300
39
1300
40
1500
41
1500
SIMOREG DC-MASTER Converter Commutation Protector
Value range
No. of
[dimension]
indices
Graduation
Factory
setting (FS)
Type
850 to 1600
Ind: None
[V]
FS=1600
1 V
Type: O2
Siemens AG
6RX1700-0DD74
Operating Instructions
12.2010
See/
change
(Access /
state)
P052 = 3
P051 = 40
online