12.2010
6.2.3

Versions to interconnect the main contactor (circuit breaker) K1

after the supply transformer
3 AC 50-60 Hz
50-60 Hz 230 V
K1
5 4
110 109
X_SCHÜTZ
XR
SIMOREG
DC-MASTER /
SINAMICS DCM
6.2.4

Recommended connection when using a Siemens 3WL circuit breaker

If circuit breakers from other manufacturers are used, then the recommended connection
described here applies accordingly.
It should be noted that the circuit breaker is equipped with a ready to close signal contact (S20,
order option Z=C22) and undervoltage release (F3 short-time delayed or F4 with the shortest
possible delay time, the version is defined using the 15th position of the MLFB of the circuit
breaker).
Also refer to the operating instructions for the 3WL circuit breaker, Order No.: 3ZX1812-0WL00-
0AN0 Chapter8.4 Auxiliary release/ electrical close inhibit
(
http://support.automation.siemens.com/WW/view/en/8912465
Siemens AG
6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector
400 V-690 V
SIMOREG CCP
before the supply transformer
3 AC 50-60 Hz
K1
400 V-690 V
SIMOREG
DC-MASTER /
SINAMICS DCM
Operating Instructions
50-60 Hz 230 V
109 110
4 5
XR
X_SCHÜTZ
3 AC 50-60 Hz
400 V-690 V
SIMOREG CCP
)
ENGLISH
Connecting
31