Siemens SIMOREG DC-MASTER Operating Instructions Manual page 63

Converter commutation protector
Table of Contents

Advertisement

12.2010
P111 should be noted and only set again after the SIMOREG CCP commissioning has been
completed.
5.
Determining the maximum energy in the armature circuit for the turn-off operation
Parameter value required:
n570
r072i002
P101
P111
as well as a characteristic diagram according to the following table:
MLFB
SIMOREG CCP
6RA7085-6FC00-0
6RA7091-6FC00-0
6RA7095-6FC00-0
6RA7090-6KC00-0
6RA7095-6KC00-0
1.) Rated DC voltage according to the motor rating plate (the values are typical rated data
for Siemens DC motors from the product catalog DA12
2.) The characteristic diagrams are provided in the appendix to these operating instructions
If the graphically determined value lies below the limit line W_max, then the energy reduction
in the armature circuit is assured using the SIMOREG CCP.
6.
Determining the setting value for parameter U578 (factory setting = 145)
Required parameter values:
n570
r071
r072i002
P078i001
P101
P111
P351
⇒ Determining the setting value according to the parameter description for U578
The SIMOREG CCP is now ready to run.
Siemens AG
6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector
MLFB (Order No.) of the SIMOREG CCP
Actual rated unit DC current, armature [A]
Rated motor armature voltage [V]
Armature circuit inductance [mH]
MLFB
characteristic
number
250
251
252
253
254
MLFB (Order No.) of the SIMOREG CCP
Rated unit supply voltage (armature) [V]
Actual rated unit DC current, armature [A]
Actual rated converter input voltage, armature [V]
Rated motor armature voltage [V]
Armature circuit inductance [mH]
Threshold for the undervoltage shutdown [%].
Operating Instructions
1.)
1.)
P101 [V]
No. of the associated
characteristic diagram
420
11
470
12
420
11
470
12
420
13
520
14.0
600
14
720
15
520
16.0
600
16
720
17
ENGLISH
Commissioning