Interpreting Beeps And Displays - Omron BU1002SW Instruction Manual

Powli
Hide thumbs Also See for BU1002SW:
Table of Contents

Advertisement

3-3

Interpreting beeps and displays

1. Displays and beeps in normal operation
Bypass
Power supply
Status
operation
No.
output
indicator
lamp
1
2
3
2. Displays and beeps while testing
4
5
3. Displays and beeps during power failure or AC input error
6
7
8
9
10
4. Displays and beeps when there is an equipment failure
11
12
Battery
Beep
Charging
replacement
lamp
lamp
None
OFF
None
ON
None
ON
OFF
None
Discharging
OFF
None
Discharging
Intermittent
OFF
4-second
Discharging
intervals
Intermittent
OFF
1-second
Discharging
intervals
OFF
None
Discharging
None
(ON)
None
(ON)
Intermittent
ON
0.5-second
discharging
intervals
ON
Continuous
discharging
Description
No AC input.
Operation stopped.
There is AC input.
Power switch is OFF.
Power switch is ON.
Operating normally.
Self-diagnostic test in progress.
Auto battery test in progress.
In Battery Mode due to power
failure or AC input error.
Output will stop if Battery
Mode continues.
(Same as above.)
Battery level is low, so output
will soon stop.
Battery is dead,
so output stopped.
(This is displayed only for
a few seconds.)
AC input voltage is too high
(over).
AC input frequency is too
high (over).
AC input voltage is too low
(under).
AC input frequency is too
low (under).
There are too many connected
devices and the rated capacity is
exceeded. If this state continues
for as long as or longer than the
times described below,
commercial power continues
to be supplied through bypass
operation (Note 1).
or
・When connection capacity is
 at 100% or higher: Bypass
 operation begins after 10 seconds
・When connection capacity is
 at 120% or higher: Output stops
 after 1 minute (Go to No.12)
・When connection capacity is
 at 140% or higher: Output stops
 after 10 seconds (Go to No.12)
Output stopped due to
or
exceeded connection capacity.
1002
3002
BU
SW / BU
(
indicates the display is OFF)
(
indicates the display is ON)
(
indicates blinking)
Solution
− −
− −
− −
− −
− −
Perform shutdown operations
for the connected devices
and stop them.
(Same as above.)
Charge the battery.
Use within the AC input
voltage/frequency range
described in the specifications.
→ See Page 90
(Same as above.)
Reduce the number of connected
devices until the display appears
as in status No. 3.
Turn OFF the power switches of
all devices connected to the unit,
reduce the number of connected
devices, and turn the power switch
back ON again.
SW
3
37