. UPS functions
● Setting for whether or not to perform battery test (setting switch 3 )
... Factory setting: OFF
OFF: The battery test is automatically executed once every 4 weeks.
ON:
Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
● Auto startup mode setting (setting switch 4 ) ... Factory setting: OFF
OFF: (Mode A)
ON: (Mode B)
* Setting switch 4 is valid when the auto startup after recovery from power failure setting (setting switch
2 ) is set to OFF (auto restart is performed).
* This setting mode is valid only after the UPS has been stopped by the contact signal backup stop
signal (BS).
* When a cable is connected to the RS-232C connector and the UPS monitoring software is used, the
unit operates in Mode A regardless of this setting.
42
ON
1
2
ON
1
2
After UPS stopped, the UPS is automatically started immediately when "ON" is
detected for the AC input.
After UPS stopped, the UPS is automatically started in the AC input's "OFF to ON"
timing that is detected.
(Defi nition of AC input OFF: When AC input is OFF for 1 second or more)