7
. Using the UPS monitoring software and contact signal
(4) Insert the contact signal card into the UPS.
(5) Connect the BUC28 cable connector (female end) to the Xserve RAID serial port and turn the connect
fi xing screw clockwise to tighten it.
Connect the other end (male end) of the same cable to the contact signal card and turn the connector
fi xing screw clockwise to tighten it.
XserveRAID
BU1002SW
Xserve
2. Procedure for changing settings so that Xserve RAID performs auto startup when UPS starts up
(1) Open RAID Admin.
(2) Select the target Xserve RAID and log in to it.
(3) After login is complete, the Settings button on the RAID Admin screen is enabled. Click this button to
open the Settings screen. (A RAID Admin administrator password is required when changing the set-
tings. Enter the password when prompted.)
(4) After the Settings screen opens, click the System tab and fi nd the Options section. In the Options sec-
tion, place a check mark in the check box next to "Auto restart after power failure."
(5) Click the OK button when fi nished.
3. Checking operation
(1) Put the UPS into Battery Mode by disconnecting the unit's AC input plug from the wall outlet (commercial
power).
(2) When in Battery Mode, the UPS outputs the power outage signal. When the Xserve RAID receives the
power outage signal, the write cache is closed.
(The write cache section on the operating system's RAID Admin data screen displays "Not in use.")
(3) Power to the Xserve RAID can be turned OFF.
(4) After checking the operation, reconnect the unit's AC input plug to the wall outlet (commercial power).
84
BUC28
cable
Contact
signal card
XserveRAID
BU3002SW
Contact
signal card
Xserve
BUC28
cable