2. Power supply output group B, C
The output start times for power supply output group B and C are independent of power supply out-
put group A, so they can be delayed or set to precede the output stop time.
The output start/stop time control funtion is available when using the included "PowerAct Pro" UPS
monitoring software, "UPS Power Manager" or "SNMP/Web card".
Output ON/OFF can be controlled with the included UPS monitoring software while the BU1002SW is
operating.
The delay settings and ON/OFF control described here can be performed independently for power
supply output group B and power supply output group C.
This function can be used to set the startup order of servers, peripheral devices, etc.
The output receptacles can also be forcibly turned ON/OFF remotely.
Power supply output group A
Power supply output group B
Power supply output group C
* In the factory setting, the time is set to 0 second.
2-3-1 Connecting a device to the power supply output (BU1002SW)
(1) Connect devices that require backup to the unit's power supply output receptacle or output terminal
block.
Make sure that the total capacity of the devices connected to the output receptacle does
not exceed the output rated capacity of the BU1002SW. If the overload indication (
displayed, reduce the number of connected devices.
BU1002SW (Rated value of output capacity: Max. 1kVA/700W)
"Power supply output" group
Group A
Group B
Group C
Group C
Output ON
Time setting
Time setting
Output receptacle
C13: 1 (Rated capacity: 15A)
C13: 1 (Rated capacity: 15A)
C13: 1 (Rated capacity: 15A)
See also
Group A
Group C
Group B
Group B
1002
BU
Output OFF
Time setting
Time setting
Output terminal block
1 line (Rated capacity: 20A)
1 line (Rated capacity: 20A)
Group control of power supply output
See Page 20