Coefficient Gain in Actual Output Frequency

Settings 0~160.00
 This parameter is to set coefficient gain in actual output frequency. Set Pr.00-04= 31 to display the
calculation result on the screen (calculation = output frequency * Pr.00-05).

Software Version

Settings Read only

Parameter Protection Password Input

Settings 1~9998, 10000~65535
Display
 This parameter allows user to enter their password (which is set in Pr.00-08) to unlock the
parameter protection and to make changes to the parameter.
 Pr.00-07 and Pr.00-08 are used to prevent the personal misoperation.
 When the user have forgotten the password, clear the setting by input 9999 and press ENTER key,
then input 9999 again and press Enter within 10 seconds. After decoding, all the settings will return
to factory setting.

Parameter Protection Password Setting

Settings 1~9998, 10000~65535
 To set a password to protect your parameter settings. If the display shows 0, no password is set
nor password has been correctly entered in Pr.00-07. All parameters can then be changed,
including Pr.00-08. The first time you can set a password directly. After successful setting of
password the display will show 1. Be sure to write down the password for later use. To cancel the
parameter lock, set the parameter to 0 after inputting correct password into Pr. 00-07.
 How to retrieve parameter protection after decoding by Pr.00-07:
Method 1: Re-enter the password to Pr.00-08 (input the password once).
Method 2: After reboots, password function will be recovered.
Method 3: Input any value into Pr.00-07 (Do not enter the password).
.
0~3 (the times of password attempts)
0: No password protection / password is entered correctly (Pr00-07)
1: Password has been set
Chapter 12 Description of Parameter SettingsC2000 Series
12-5
Factory Setting: 0
Factory Setting: #.#
Factory Setting: 0
Factory Setting: 0