Cabinet Ac Power Considerations; Cabinet Ac Power Component Requirements For Wall Mounted Systems - Toshiba STRATA CTX100 Installation And Maintenance Manual

Digital business telephone systems
Hide thumbs Also See for STRATA CTX100:
Table of Contents

Advertisement

Strata CTX670 Installation
Install AC Power Components

Cabinet AC Power Considerations

The CTX670 power supply works with either 120VAC, 208VAC or 240VAC. CTX670 only
requires 120VAC (up to three cabinets if one AC cord is allowed or five cabinets if two AC cords
are allowed – see below).
In the case where system has more then five cabinets, 208VAC or 240AVC is required for the
primary AC power source. 208VAC or 240VAC can always be optionally used for systems with
five or less cabinets for future growth or, if the electrical code requires.
To determine AC power requirements, it is necessary to check local electrical code requirements
for 120VAC, 208VAC or 240VAC primary power. Some electrical codes stipulate that:
208VAC or 240VAC is required for telephones systems
Only one electrical cord can connect to the telephone system.
Only two electrical cords can connect to the telephone system.
No electrical cord can connect to the telephone system – must use conduit wiring installed by a
certified electrician (example: when system is floor mounted).
Cabinet AC Power Component Requirements for Wall Mounted
Systems
Tables 3-2
configurations of the CTX670 cabinets.
Table 3-2
Wall Mount Cabinet Power Component Requirements for 120VAC Primary Power
Local Electrical Code
Allows only one 120VAC
power cord from system
Allows two 120VAC
power cords from system
• One dedicated, isolated, 20 amp. AC circuit breaker with dual outlets is required.
• N/A= If the system contains more than three cabinets and if the local code allows only one AC cord, the system
requires a BCCB120 conduit box wired by a certified electrician when using 120VAC as primary power. Otherwise,
208VAC or 240VAC should be used as the primary power source (see cabinet power options listed below).
Table 3-3
Wall Mount Cabinet Power Component Requirements for 208VAC or
240VAC Primary Power
Local Electrical
Code
Allows One AC
power cord from
system
Important!
3-24
and
3-3
show the cabinet parts required to distribute AC power for various
1 Cabinet
2 Cabinets
0 RPSB2
1 RPSB2
0 RPSB2
0 RPSB2
1 Cabinet
2 Cabinets
1 BPSB240
1 BACL240
2 BACL240
The plugs and wall receptacles required by the local electrical code might differ for
208VAC and 240VAC. Thus in some areas of the U.S., the plug used on the Toshiba
240VAC power strip and 240VAC power supply cord (NEMA code 6-20P) can not
be used for 208VAC installations. In this case, when using 208VAC, the AC plugs on
the BPSB240 power strip cord that connects directly to the 208VAC wall outlet must
be changed by a certified electrician per the local electrical code.
Figures 3-14~3-17
show how to install these parts.
3 Cabinets
4 Cabinets
1 RPSB2
N/A
1 RPSB2
1 RPSB2
3 Cabinets
4 Cabinets
1 BPSB240
2 BPSB240
3 BACL240
4 BACL240
5 Cabinets
6 Cabinets
N/A
N/A
2 RPSB2
N/A
5 Cabinets
6 Cabinets
2 BPSB240
3 BPSB240
5 BACL240
6 BACL240
Strata CTX I&M
7 Cabinets
N/A
N/A
7 Cabinets
3 BPSB240
7 BACL240
10/02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Strata ctx670

Table of Contents