Preparing the Area

1.5.1

Enterprise 6500/5500 Cabinet Systems

Server cabinets require approximately 4 feet (120 cm) of space in front and 3 feet
(90 cm) in back (
Server and expansion cabinets can be placed next to each other, without space
between them, since there are no side clearance requirements during operation.
To access and remove side panels, however, allow approximately 1 foot (30 cm) of
space on the sides.
The server system (including expansion cabinets) should have a dedicated AC
breaker panel. The server system should not share this breaker panel with other,
unrelated equipment.
Keep power and interface cables out of the way of foot traffic. Cables can be
routed inside walls, floors, ceilings, or in protective channels. Interface cables
should be routed away from motors and other sources of electric/magnetic or
radio frequency interference.
If the cabinet is installed on a raised floor, conditioned air should be directed to
the bottom of each rack through perforated panels.
Refer to the Sun Microsystems Data Center Site Planning Guide, Data Centers' Best
Practices (805-5863) for more information on the recommended optimal operating
environment.
Tape/disk
Tape/disk
EXP
EXP
FIGURE 1-5
) for access by service personnel.
FIGURE 1-5
3 feet access at rear
1 foot, at left
and right sides
(for access only)
System
cabinet
Tape/disk
EXP
4 feet access at front
Cabinet Server Access Areas — Top View
Tape/disk
Tape/disk
EXP
NOTE: During operation, system and expansion
cabinets can be side by side –with 0 clearance–
since there are no side clearance requirements.
Chapter 1
Tape/disk
EXP
EXP
Preparing for Installation
1-9