Floor Clearance - Vermont Castings PH24 Appliance Installation And Operating Instructions

Unvented gas log heater/ vented decorative
Table of Contents

Advertisement

PH Gas Logs
The gas log heater must be installed at least 5" above
any combustible fl ooring material, such as carpeting or
tile, which is closer than 14" to the base of the fi replace.
The minimum distance must be maintained from the top
surface of carpeting, tile, etc. Figure 8
OR,
10
FP2924
Figure 8 -
Minimum Clearance Above Combustible Flooring
This
Distance
May Now
be Less
than 5"
FP2925
Figure 9 -
Minimum Clearance Above Combustible Flooring with
Noncombustible Material Installed at Base of Fireplace
The gas log heater may be installed nearer to the fl oor if a
minimum of 14" of noncombustible material such as slate
or marble is installed between the base of the fi replace and
the combustible fl ooring. Figure 9
Heater in Fireplace
or Firebox
Combustible
Material
5" Minimum
Heater in
Fireplace or
Firebox
Combustible
Material
14" Minimum

FLOOR CLEARANCE